5) Triggering the reading/writing of data
Method 1:
Users can use the instruction TO in ISPSoft to trigger the reading of data from bit devices/word
devices, and the writing of data into bit devices/word devices. (CR#7,CR#8, CR#17, and CR#18)
CR# Attribute
Triggering the reading
7
R/W
of data through COM1
Triggering the reading
17
R/W
of data through COM2
Triggering the writing of
8
R/W
data through COM1
Triggering the writing of
18
R/W
data through COM2
If users want to continually trigger the reading of data from word devices, they can write 2 into
CR#17. If users wan to trigger the reading of data from word devices once, they can write 1 into
CR#17.
If users want to continually trigger the writing of data into word devices, they can write 2 into
CR#18. If users wan to trigger the writing of data into word devices once, they can write 1 into
CR#18.
Ch ap te r 8 Ser ia l C om mu nic a ti on Mod ul e AH1 0/15 SC M
Register name
High byte: Reading data from bit devices
Low byte: Reading data from word devices
0: Not triggering it
1: Triggering it once
2: Always triggering it
High byte: Reading data from bit devices
Low byte: Reading data from word devices
0: Not triggering it
1: Triggering it once
2: Always triggering it
High byte: Writing data into bit devices
Low byte: Writing data into word devices
0: Not triggering it
1: Triggering it once
2: Always triggering it
High byte: Writing data into bit devices
Low byte: Writing data into word devices
0: Not triggering it
1: Triggering it once
2: Always triggering it
Description
8 - 4 3