 Setting of AH08AD-5C
After configuring AH08AD-5C, refer to Figure 3 for the related parameters setting.
Explanation of the options above
Name
rack
slot
CH0~CH7 Input
mode
CH0~CH7 Input
average time
Chapter 14 Remote I/O Communication Module AHRTU-PFBS
Figure 3
Setting
The number of the rack where the I/O module is
(Rack number ranges from 1 to 8, 1 represents
0x01
the main rack, 2~8 stand for extension racks and
the slot number is 0~11.)
The number of the slot on the rack where the I/O
module is. (Rack number ranges from 1 to 8, 1
0x02
represents the main rack, 2~8 stand for extension
racks and the slot number is 0~11).
The input channel mode of AH08AD-5C is
disable
disabled by default.
0mA~20mA
Mode: disable
4mA~20mA
Mode: 0mA~20mA
+20mA~-20m
Mode: 4mA~20mA
A
Mode: +20mA~-20mA
0x0A
Average times setting for CH0~ CH7 input
Explanation