Chapter 14 Remote I/O Communication Module AHRTU-PFBS
The following window contains the offset address of I/O modules that AHRTU-PFBS-5A configures.
That is the offsets of the starting addresses of INPUT area and OUTPUT area that AH master PLC
assigns to the master module with Byte as the unit.
The D device in PLC regards Word as the unit, the offset address regards Byte as the unit and
therefore the counting of the starting D register in the master PLC that the configured module of the
slave corresponds to:
The starting number of the D registers in OUTPUT area of the master PLC corresponding to the
slave configured module = the starting address in OUTPUT area + (Address/2).
The starting number of the D registers in INPUT area of the master PLC corresponding to the slave
configured module = the starting address in INPUT area + (Address/2).
The offset address of each module can also be assigned manually by not ticking "Auto addressing"
on the ablove interface but inputing the value of offset address in Address column.
14-47