AH5 00 M od ul e M anua l
Type
Telegram to the power meter
All measured values
5
(via a control record)
Output parameters
6
(via a control record)
Statuses
7
(via a control record)
Instrument specifications
8
(via a control record)
Real-time clock values
9
(via a control record)
(4) Editing UD Link
Type 1: Sending an abbreviated record
『Start bit』 + 『Instrument address (IA)』 + 『Function field (FF)』 + 『Checksum (CS)』 + 『End mark』
16#10+D0+16#09+(IA+FF)+16#16
Start bit: 16#10
Function field (FF): 16#09
8 - 5 0
Response (via a record type)
Full record
Full record
Full record
Full record
Full record
The instrument address (IA) is read from
D0.
Checksum (1 byte): IA+FF