Delta AH500 Manual page 696

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

AH500 Module Manual
Explanation of the options above
Name
rack
slot
CH0~CH3 Input
mode
CH0~CH1 Output
mode
CH0~CH3 Input
average time
CH0 output hold
CH1 output hold
The conversion between the analog quantity and digital quantity for all modules that
AHRTU-PFBS-5A supports:
14-66
Setting
The number of the rack where the I/O module are
placed (Rack number is 1~8, 1 represents the
0x01
main rack, 2~8 are extension racks and the slot
number is 0~11.)
The number of the slot on the rack where the I/O
module is. (Rack number is 1~8, 1 represents the
0x07
main rack, 2~8 are extension racks and the slot
number is 0~11).
The input channel mode of AH06XA-5A is
disabled by default.
disable
Mode: disable
-10V~+10V
Mode: -10V~+10V
0V~10V
Mode: 0V~10V
-5V~+5V
Mode: -5V~+5V
0V~+5V
Mode: 0V~+5V
1V~+5V
Mode: 1V~+5V
0mA~20mA
Mode: 0mA~20mA
4mA~20mA
Mode: 4mA~20mA
-20mA~20mA
Mode: -20mA~20mA
The output channel mode of AH06XA-5A is
disabled by default.
disable
Mode: disable,
-10V~+10V
Mode: -10V~+10V
0V~10V
Mode: 0V~10V
-5V~+5V
Mode: -5V~+5V
0V~+5V
Mode: 0V~+5V
1V~+5V
Mode: 1V~+5V
0mA~20mA
Mode: 0mA~20mA
4mA~20mA
Mode: 4mA~20mA
1~100
Average times setting, default value 10
Output hold options
Enable: the output of other I/O modules of
AHRTU-PFBS-5A is held when some I/O module
has a fault and the master is disconnected or
disable/enable
stops running.
Disable: the output of other I/O modules of
AHRTU-PFBS-5A is cleared to 0 when some I/O
module has a fault and the master is
disconnected or stops running.
Output hold options
Enable: the output of other I/O modules of
AHRTU-PFBS-5A is held when some I/O module
has a fault and the master is disconnected or
disable/enable
stops running.
Disable: the output of other I/O modules of
AHRTU-PFBS-5A is cleared to 0 when some I/O
module has a fault and the master is
disconnected or stops running.
Explanation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents