AH500 Module Manual
Tighten the screw of the communication connector to
fix the cable to the holes of the connector with a
standard slotted screwdriver.
Installing the DeviceNet Connector
11.3.4
After wiring is over, insert the DeviceNet connector to the interface.
Tighten the screws of the two sides of the DeviceNet terminals.
Note:
The cable should be away from the power wire to decrease the electromagnetic interference.
The two ends of the shielded wire should be grounded.
The 121 ohm resistor should be connected between the white and blue signal wires.
DeviceNet Bus Transmission Distance and Network
11.3.5
Topology Structure
DeviceNet bus transmission distance is determined by the DeviceNet bus transmission speed.
See the following table on different transmission speed and the corresponding maximum
communication distance.
Transmission
speed (bit/second)
Maximum
communication
distance
11-12
10K
20K
50K
5000
2500
1000
125K
250K
500K
500
250
100
800K
1M
50
25