the master is downloading the configuration, 80 and its node address are shown on the
seven-segment display of AHRTU-DNET-5A alternately; While AHRTU-DNET-5A configuration
is being downloaded, 83 and its node address are shown alternately; while AH10SCM-5A serial
port data configuration is being downloaded, 84 and its node address are shown alternately.
 Monitor and Check
After configuration and download are completed, check if AHRTU-DNET-5A works normally. If
AHRTU-DNET-5A is in normal operation, the digital displays of the master and
AHRTU-DNET-5A show their own node addresses; MS and NS indicators are green constantly.
11.5 Application Example
This section is going to describe how to configure the I/O module parameters in AHRTU-DNET-5A
and the I/O mapping relations between AHRTU-DNET-5A and AH10DNET-5A with one application
example.
Control requirement
1. Capable of setting the input voltage of channel 1 of AH06XA-5A through the CPU automatically
2. When the input voltage of channel 1 of AH06XA-5A>5 V, the input indicator Y0.0 of
AH16AP11T-5A is on and the output indicator Y0.1 is OFF.
3. When the input voltage of channel 1 of AH06XA-5A<&=5 V, the input indicator Y0.0 of
AH16AP11T-5A is off and the output indicator Y0.1 is ON.
11.5.1 Network Structure
Note:
1. Before configuring AHRTU-DNET-5A, use HWCONFIG configuration interface via the ISPSoft
software to configure AH10DNET-5A module to AHCPU530-EN and download it.
2. Connect the output of channel 1 of 08DA to the input of channel 1 of AH06XA-5A by using the
hardware; add 24 V power to AH04DA-5A and AH06XA-5A respectively.