AH500 Module Manual
Explanation of "AHRTU-DNET Setup" interface:
Item
Output start
It is the initial output address of AHRTU-DNET-5A and
device
occupies one word.
It is the initial input address of AHRTU-DNET-5A and occupies
Input start device
one word.
When loses
When being disconnected from the DeviceNet network, how
DeviceNet
AHRTU-DNET-5A will treat the error. Options "RTU keep
connection
running" and "RTU stop running" are for selection.
When detecting that an error occurs in any one of I/O
When I/O module
modules, how AHRTU-DNET-5A will treat the error. Options
error
"RTU keep running" and "RTU stop running" are for selection.
Setup of the extended baud rate of AHRTU-DNET-5A. Pick the
item so as to set the extended baud rate of AHRTU-DNET-5A.
Software baud
Download and save the data to AHRTU-DNET-5A. Only when
rate
both of DR1 and DR0 switches are ON, the extended baud
rate will be effective.
Firmware version
To show the firmware version of AHRTU-DNET-5A
Note: When error treatment setting of AHRTU-DNET-5A is inconsistent with exception handling of
each I/O module, option "RTU stop running" is selected in priority.
11.4.2.4

I/O Module Configuration Interface

Double click I/O modules to set the parameter mapping configuration of each module on the
"AHRTU-DNET Configuration" interface.
11-30
Explanation
Default
-
-
RTU
keep
running
RTU
keep
running
-
-