External wiring
(1) AH04AD-5A/AH08AD-5A
Four-wire connection: Voltage input
-10V ~+10V
+
+24V
-
0V
Four-wire connection: Current input
-20mA~+20mA
+
+24V
-
0V
Two-wire connect ion: Current input
4mA~+20mA
+24V
+
-
0V
Three-wire connection: Voltage input
-10V ~+10V
+24V
+
-
0V
Three-wrie connection: Current input
-20mA~+20mA
+24V
+
-
0V
*1. Please use a shielded cable as an analog input cable, and isolate the shielded cable from other power
cables.
*2. If current is connected, the connection between Vn+ and In+ needs to be a short circuit. (n is in the range of
0 to 7.)
*3. If ripple voltage results in interference with the wiring, please connect a 0.1~0.47 μF and 25 V capacitor.
*4. Please connect the ground in the shielded cable to the terminal SG.
*5. Once AH04AD-5A/AH08AD-5A is installed on a backplane, the connection between the terminal SG on
AH04AD-5A/AH08AD-5A and the terminal
terminal
on the backplane to the ground terminal
Ch ap te r 2 Ana lo g In pu t M odule AH04 AD /AH0 8AD
CH0
Shielded cable*1
*3
*4
SG
CH1
Shielded cable*1
*2
*4
SG
Shielded cable*1
CH2
*2
*4
SG
Shielded cable*1
CH3
*4
SG
Shielded cable*1
CH4
*2
*4
SG
*5
DC24V
on the backplane will be a short circuit. Please connect the
1M
V0+
250
I0+
1M
VI0-
1M
V1+
250
I1+
1M
VI1-
1M
V2+
250
I2+
1M
VI2-
1M
V3+
250
I3+
1M
VI3-
1M
V4+
250
I4+
1M
VI4-
SG
DC/DC
ZP
converter
UP
.
AG
CH0
AG
CH1
AG
CH2
AG
CH3
AG
CH4
+15V
AG
-15V
2 - 1 7