AH500 Module Manual
Explanation of the options above
Name
rack
slot
CH0~CH7 Output
mode
CH0~CH7 output
hold
The conversion between the analog quantity and digital quantity for all modules that
AHRTU-PFBS-5A supports:
When the input/ output mode of the analog module is positive voltage or positive current,
the corresponding digital value is 0 ~32000; for example, if the modes are 0V~10V and
4mA~20mA, the corresponding digital values are both 0~32000.
14-68
Setting
The number of the rack where the I/O module are
placed (Rack number is 1~8, 1 represents the
0x02
main rack, 2~8 are extension racks and the slot
number is 0~11.)
The number of the slot on the rack where the I/O
module is. (Rack number is 1~8, 1 represents the
0x02
main rack, 2~8 are extension racks and the slot
number is 0~11).
The output channel mode of AH08DA-5B is
disabled by default.
disable
Mode: disable
-10V~+10V
Mode: -10V~+10V
0V~10V
Mode: 0V~10V
5V~+5V
Mode: -5V~+5V
0V~+5V
Mode: 0V~+5V
1V~+5V
Mode: 1V~+5V
Output hold options:
Enable: the output of other I/O modules of
AHRTU-PFBS-5A is held when some I/O module
has a fault and the master is disconnected or
disable/enable
stops running.
Disable: the output of other I/O modules of
AHRTU-PFBS-5A is cleared to 0 when some I/O
module has a fault and the master is
disconnected or stops running.
Explanation