4. Click "OK" to download the configuration to the scanner module. At the moment, the
configuration of the DeviceNet network is completed.

10.9.5 Data Flow Direction

Configure the DeviceNet network following the above steps and the mapping relation between
AH10DNET-5A and the slave device is shown below:
AH500 series CPU module → AH10DNET-5A → Slave device
AHCPU510-EN
D1505
D1506
D1507
D1508
D1509
AH500 series CPU module ← AH10DNET-5A ← Slave device
AHCPU510-EN
D1005
D1006
D1007
D1008
D1009
Note: AHCPU510-EN is to monitor and control D0 in AHCPU530-EN via the DeviceNet bus; move
the value in D2000 to D0 and meanwhile move the value in D0 to D2500 in AHCPU530-EN in
real time.
Ch a pt er 1 0 De v ic eN e t Com m unic at i on Mo d ul e A H 10 DN ET
AH10DNET-5A
AH10DNET-5A
(Master)
AH10DNET-5A
AH10DNET-5A
(Master)
AHCPU530-EN
(Slave)
D2000
D2001
D2002
D2003
D2004
AHCPU530-EN
(Slave)
D2500
D2501
D2502
D2503
D2504
1 0 - 5 7