Delta AH500 Manual page 752

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

AH500 Module Manual
16.1
Introduction to AHRTU-ETHN-5A
Thank you for choosing Delta AHRTU-ETHN-5A module. Please read the product instruction
carefully before use so as to install and operate the product properly.
AHRTU-ETHN-5A is AH series remote I/O module. AH series CPU such as AHCPU5x1-EN of V2.0
and above can easily control AH digital I/O module and analog I/O module through EtherNet/IP
communication protocol.
16.1.1 Function
Supports the standard EtherNet/IP communication protocol slave, I/O connection through
cyclic data exchange as well as explicit message connection through acyclic data exchange.
Provides module status (MS), network status (NS), I/O module status and a seven-segment
display showing AHRTU-ETHN-5A's status and error code.
Provides AHRTU error processing mechanism by setting how to process I/O modules and
AHCPU when an error occurs in I/O modules.
Able to connect 1 main backplane and 7 extension backplanes. Max. 68 AH series I/O
modules are connectable to AHRTU-ETHN-5A. Max. number of input and output points and
max. number of channels are 3744 and 544 respectively.
16.1.2
Specification
Electrical specification
Item
Power supply voltage
Power consumption
Weight
Ethernet
Item
Communication
protocol
Service supported
Baud rate
Communication
interface
Number of Ethernet
ports
MODBUS TCP
General
MODBUS TCP
Server
EtherNet/IP
General
CIP service type_ IO
Connection
16-2
5 VDC
2.16 W
160g
EtherNet/IP, MODBUS TCP
BOOTP, DHCP, NTP
10/100 Mbps Auto-Detection
RJ-45 with Auto MDI/MDIX
2 (X1, X2)
Item
Equipment type
Topology supported
Max. number of Modbus
TCP connections
Item
Equipment type
Topology supported
Max. number of CIP
connections
Max. number of TCP
connections
Specification
Specification
Specification
Server
Star and linear
32
Specification
Adapter
Star, linear and ring
96
48 (
Servers)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents