Monitoring Via The Software - Delta AH500 Manual

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

Notes:
1. Write 16#0002 to D1006 for always reading the word device; write 16#0001 to D1006 for only
reading once. Write 16#0002 to D1007 for always writing to word device and write 16#001 to
D1007 for only writing once.
2. Write 16#0200 to D1006 for always reading bit device and write 16#0100 to D1006 for only
reading once. Write 16#0200 to D1007 for always writing to bit device and write 16#0100 to
D1007 for only writing once.
3. Writing 1 to D1011 indicates to trigger and execute the content of Group ID 1. After the
execution is over, D1011 is cleared as 0. If the default value in D1011 is 0, no group will be
triggered.
4. Write the number of times to D1013. If the number 0 is written, no execution or the stopping
state occurs; 1~254 can be the execution times; 255 (16#FF) indicates the action is always
executed.
11.6.3.2

Monitoring via the Software

On the AHRTU-DNET-5A configuration interface, click "Start Monitor" button to monitor the
operational state of AH10SCM-5A.
Ch a pt er 11 DeviceNet Re m ote I/O Module AHRTU-DNET
11-101