Ch a pt er 5 Tem per at ur e M eas ur em ent Mo d u l e A H 04 PT / AH 0 8 PT G
(3) Please connect a shielded cable and a hermetically sealed cable with the ground
separately.
(4) Terminals with insulation sleeves can not be arranged as a terminal block. It is
recommended that the terminals be covered with insulation tubes.
(5) The diameters of the input/output cables used should be in the range of 30 AWG to 24 AWG
(0.3 mm to 0.6 mm). The lengths of the plastic jackets removed should be in the range of 7
mm to 8 mm. The specifications for the terminals on AH08PTG-5A and the wiring of the
terminals are shown below. The temperature of the copper lead wires used should be
60/75°C.
External wiring
(1) AH08PTG-5A
Ω
0 ~300
N i10 0/Ni10 00
P t10 0/Pt1 000
2-Wire
Ω
0~3 00
Ni 100/Ni 1000
Pt100/Pt1000
3-Wire
Ni1 00/Ni1 000
Pt1 00/Pt1 000* 2
4-Wire
Ω
0~3 00
Ni 100/Ni 1000
Pt100/Pt1000
3-Wire
*1. The cables or the shielded twisted pair cables for Ni100/Ni1000/Pt100/Pt1000 temperature
sensors are used, and should be kept separate from other power cables and cables which
generate noise. Please use a three-wire temperature sensor. If users want to use a two-wire
3 0 -2 4 AWG
0 .3 -0 .6 mm
*
C H0
Sh iel de d cab le 1
O0+
I0+
I 0-
O 0-
F G
*
C H1
Sh iel de d cab le 1
O1+
I1+
I1 -
O 1-
F G
*
C H2
Sh iel de d cab le 1
O2+
I2+
I 2-
O 2-
F G
*
C H3
Sh iel de d cab le 1
O3+
I3+
I3 -
O 3-
F G
471.5u
A
(N i100Pt100,
,
R es istor)/
204.8uA
(Pt1000)* 3
+
ADC
-
INA
AG
471.5u
A
(N i100Pt100,
,
R es istor)/
204.8uA
(Pt1000)* 3
+
ADC
-
INA
AG
5 - 5 3