AH5 00 Mod ule Manua l
Information elements
Single command
SCO: CP8{SCS, BS1, QU, S/E}
bit
8
S/E
Description
Description
Description
Double command
DCO:CP8{DCS, QU, S/E}
bit
8
S/E
Description
Refer to the SCO section for more details on S/E and QU.
Regulating step command
RCO: CP8{RCS, QU, S/E}
bit
8
S/E
Description
Refer to the SCO section for more details on S/E and QU.
9 - 2 2
7
6
5
4
QU
SCS: Single command state
0: OFF
1: ON
QU:
Qualifier for the commands
0: Unspecified
1: Short pulse
2: Long pulse
3: Persistent output
4...8:Reserved for standard definitions of companion standard (compatible
range)
9...15:Reserved for the selection of other predefined functions
16...31:Reserved for special use (private range)
S/E: Select/execute state
0: Execute
1: Select
7
6
5
4
QU
DCS: Double command state
0: Indeterminate
1: OFF
2: ON
3: Indeterminate
7
6
5
4
QU
RCS:
Status information of the step command
0: Not allowed
1: Step decrement
2: Step
increment
3: Not allowed
3
2
1
RES
SCS
3
2
1
DCS
3
2
1
RCS