15.6

Error Diagnostics and Troubleshooting

15.6.1 LED Indicators and Troubleshooting
AH10COPM-5A has two LED indicators—a RUN LED indicator and an ERROR LED indicator. The
LED indicators indicate the current states of the module.
RUN LED indicator
LED indicator
The light is OFF.
The green light
flashes once.
The green light
blinks.
The green light is
ON.
Difference between the green light which flashes once and the green light which blinks:
ON
T he green li ght fl as hes once.
OF F
ON
T he green li ght blinks.
200 ms
OF F
Ch a pt er 1 5 C AN o pe n Communication M o du l e AH 1 0CO P M
Description
AH10COPM-5A is
disconnected.
AH10COPM-5A stops
running.
AH10COPM-5A is
ready to operate.
AH10COPM-5A is
operational.
200 ms
200 ms
200 ms
Solution
Check whether the AH500 system used is
powered.
AH10COPM-5A is downloading a network
configuration, and waits to complete the
downloading of the network configuration.
If the green light is blinking when the AH500
series CPU module is running, users have to
1.
check whether the bus cable on the
CANopen network created is connected
correctly.
2.
check whether the serial communication
speed of the master station selected is
the same as the serial communication
speeds of the other slave stations.
3.
check whether the slave stations
configured are connected to the network
created.
4.
check whether slave stations are offline.
No solution is required.
1000 ms