As the two interfaces above show, the starting addresses of the INPUT and OUTPUT areas that
AH PLC assigns to the master module are D1000 and D6000 respectively. On the above interface,
the input offset address for 4 word input is 0 and the corresponding starting number of D registers
in the master PLC is 1000(1000=1000+0/2). The input offset address for 2 word input is 8 and
the corresponding starting number of D registers in the master PLC is 1004(1004=1000+8/2).
The output offset address for 4 word output is 0 and the corresponding starting number of D
registers in the master PLC is 6000(6000=6000+0/2); the output offset address for 2 word
output is 8 and the corresponding starting number of D registers in the master PLC is 6004
(6004=6000+8/2).
I/O mapping relations between master PLC and slave PLC
Register in master PLC
D6000
D6001
D6002
D6003
D6004
D6005
Register in master PLC
D1000
D1001
D1002
D1003
D1004
D1005
Note: The PROFIBUS DP data are transmitted in cycle.
Ch a pt er 1 2 N e t wor k Mo d u le AH 10 P F BM
Register in slave PLC
Register in slave PLC
D300
D301
D302
D303
D600
D601
D200
D201
D202
D203
D500
D501
1 2 - 4 9