LED status
Red light ON
Hardware error

11.7.2 Digital Display Diagnosis

LED status
The node address of
0~63
AHRTU-DNET-5A when it
works normally
Its station number is
duplicated with that of other
F0
node or exceeds the valid
range.
No module setting has been
F1
configured to
AHRTU-DNET-5A.
The work voltage of
F2
AHRTU-DNET-5A is too low.
AHRTU-DNET-5A enters the
F3
test mode.
AHRTU-DNET-5A enters the
F4
Bus-Off state.
F5
No network power
Internal error; internal storage
F6
detection error
Internal error; data exchange
F7
unit error
Error produced in factory
F8
manufacturing
Internal error; FLASH access
F9
error
FA
Main rack error
FB
Invalid configuration data
E4
Module error
Ch a pt er 11 DeviceNet Re m ote I/O Module AHRTU-DNET
Indication
Indication
--
Ensure that the node address is unique and
repower it after modifying the node address.
Configure the module and then download it to
AHRTU-DNET-5A.
Check if the work power of AHRTU-DNET-5A is
normal.
Repower AHRTU-DNET-5A.
1. Check if the network cable is normal and the
2. Check if the baud rate of the node
3. Check if the two ends of the network have
4. Repower AHRTU-DNET-5A.
Make sure the cable is correctly connected and
check if the network power is normal.
If the error still exists after repower, send your
AHRTU-DNET-5A back to the factory for repair.
If the error still exists after repower, send your
AHRTU-DNET-5A back to the factory for repair.
If the error still exists after repower, send your
AHRTU-DNET-5A back to the factory for repair.
If the error still exists after repower, send your
AHRTU-DNET-5A back to the factory for repair.
1. Check the connection of the main rack and
2. Replace the main rack with a new one.
Ensure that the network is normal and
re-download the configuration; ensure the node
address of AHRTU-DNET-5A is different from
that of other node.
The corresponding module connected to the rack
slot is in error state; check if the corresponding
module alarms or is bus-off or does not fit the
configured module or has been added to the scan
list.
How to deal with
Send it back to the factory for repair if the
error still exists after repowering
AHRTU-DNET-5A.
How to deal with
shielded wire has been grounded.
equipment on the network is the same.
been connected with one 121 Ω resistor
respectively.
replace it with a new one.
11-105