AH500 Module Manual
Explanation of AHRTU-DNET-5A configuration interface:
Item
To detect all modules currently inserted to the I/O slots of the rack. The
modules saved on the software will be compared with the modules
actually inserted to the I/O slots of the rack and the inconsistency will be
displayed with the abnormal icons. When the I/O slot of the rack on the
Scan
software is empty, the module actually connected to the I/O slot of the
rack will be displayed. If the rack information is not consistent with the
actual rack information, the previously saved module information on the
software will be deleted and the actual rack information and the modules
actually inserted to the I/O slots of the rack will be displayed.
It is an opposite action to the download. To upload and display current
AHRTU-DNET-5A configuration to the software interface, which includes
Upload
the I/O list, I/O configuration information, parameter mapping and the
basic control information of AHRTU-DNET-5A.
To download and save the AHRTU-DNET-5A configuration to
AHRTU-DNET-5A, which includes the I/O list, I/O configuration
Download
information, parameter mapping and the basic control information of
AHRTU-DNET-5A. The configuration is retained when power OFF.
To download and save the configuration of the serial port data exchange
of AH10SCM-5A to AH10SCM-5A, which contains all Modbus
Download
configuration or UD Link configuration of COM1 and COM2.
SCM
The configuration is retained when power OFF.
Reset
To make the connected AHRTU-DNET-5A restart up once.
Clear the configuration stored in the latched area, reset automatically and
Clear config
F1 appears on the indicator after resetting.
To find and set current exchange data already configured in system in
Start Monitor
real time, change the output data, find the input data in real time and use
the control word to control the running state of AHRTU-DNET-5A.
Automatically allocate the mapping address and allocate the offset of
mapping parameters in order.
Auto-Addr
When no selection of mapping parameter is set for user in AIAO module
data, system only recognizes the allocated offset of the mapping
parameters.
To clear the address allocation of all modules.
Clear-Addr
After clicking this button the mapping addresses of all modules can be
reallocated.
Select and set the mapping range of each module on the rack. The start
Rack 1
offset of mapping range can be set and the length depends on the
quantity of the register mapped by the module parameter.
To set the mapping range of serial port data exchange of AH10SCM-5A,
SCM
the start offset and length. Input and output mapping length are both 20
words.
Slot
The serial number of the slot of the module on the rack
Name
The name of the module
The firmware version of the module.
Through selecting the corresponding firmware version, download the
Firmware
module parameter information which matches the firmware version of the
module.
Description
Describe the basic information of each module
The input data mapping range of each module which depends on the
Input
start address offset and length of input mapping data
11-24