Ch a pt er 11 DeviceNet Re m ote I/O Module AHRTU-DNET
Parameter editing of write and read of Modbus is shown as below.
AH10SCM-5A reads the value of the address 2103 (hex) of the AC motor drive via the serial port;
the read value will be transmitted to AHRTU-DNET-5A via the rack; AHRTU-DNET-5A will
transmit the data to AH10DNET-5A along the DeviceNet bus and AH10DNET-5A will transmit
the data to D1540 of AH500 series PLC via the rack.
The values in D1020 and D1021 of AH500 series PLC are transmitted to AH10DNET-5A via the
rack; AH10DNET-5A will transmit the data to AHRTU-DNET-5A along the bus;
AHRTU-DNET-5A will transmit the data to AH10SCM-5A via the rack and AH10SCM-5A will
write the data to the addresses 2000 (hex) and 2001 (hex) of the AC motor drive via the serial
port.