10.10.2 Seven-segment Display Diagnosis
Code
Node address of DVPDNET-SL
0~63
(in normal operation)
80
AH10DNET-5A in STOP status.
The node address of
AH10DNET-5A is identical to
F0
that of other node or exceeds
the valid range.
No slave device is configured in
F1
the scan list of AH10DNET-5A
Excessively low voltage for
F2
AH10DNET-5A
F3
Entering test mode
F4
Bus-off
F5
No network power
Internal errors; internal memory
F6
unit errors
F7
Data exchange unit errors
Sequence number detection
F8
errors
An error in reading/writing the
F9
configuration data.
The node address of
AH10DNET-5A is the same as
FA
that of the slave configured in
the scan list.
Ch a pt er 1 0 De v ic eN e t Com m unic at i on Mo d ul e A H 10 DN ET
Indication
Duplicate ID
detection has not
completed.
Duplicate ID
detection failed or
bus-off.
No network power
Hardware error
Indication
1. Ensure that the node address of
2. Repower it after changing its node address.
1. Check if the network cable is normal and the
2. Check if the baud rates of all node equipment
3. Check if both of the two ends of the network
4. Repower AH10DNET-5A.
How to deal with
Ensure that at least one node and
AH10DNET-5A have the same baud rate
and communicate normally on the network.
1. Ensure that the node address of
AH10DNET-5A is unique.
2. Repower it.
1. Check if the network cable connection is
correct.
2. Check if the network power is normal.
Return it to the factory for repair.
How to deal with
--
Turn the AH500 series CPU module to RUN
and start I/O data exchange.
AH10DNET-5A is unique.
Configure the slave in the scan list and
download the scan list to AH10DNET-5A.
Check if the power supply for AH10DNET-5A
and the AH500 series CPU module is normal.
Switch IN1 from ON to OFF and repower
AH10DNET-5A.
shielded wire has been grounded.
on the network are consistent.
have a 121 Ω resistor.
Make sure the cable is correctly connected and
check if the network power is normal.
If the error still exists after power on again, send
your AH10DNET-5A back to the factory for
repair.
If the error still exists after power on again, send
your AH10DNET-5A back to the factory for
repair.
If the error still exists after power on again, send
your AH10DNET-5A back to the factory for
repair.
If the error still exists after power on again, send
your AH10DNET-5A back to the factory for
repair.
Method 1: Reset the node address of
AH10DNET-5A, which must be different from
that of the slave configured in the scan list and
then repower it.