80 Motor control and I/O board (RMIO)

Relay outputs

Switching capacity
Minimum continuous current
Maximum continuous current
Insulation test voltage

DDCS fiber-optic link

24 V DC power input
Voltage
Typical current consumption
(without optional modules)
Maximum current consumption 1200 mA (with optional modules inserted)
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfill the
Protective Extra Low Voltage (PELV) requirements stated in EN 50178 provided that the external
circuits connected to the terminals also fulfill the requirements and the installation site is below
2000 m (6562 ft). Above 2000 m (6562 ft), see page
Three programmable relay outputs
8 A at 24 V DC or 250 VAC, 0.4 A at 120 V DC
5 mA rms at 24 V DC
2 A rms
4 kV AC, 1 minute
With optional communication adapter module RDCO. Protocol: DDCS
(ABB Distributed Drives Communication System)
24 V DC ± 10%
250 mA
.