Supply Connection; Disconnecting Device; Fuses; Main Contactor - ABB ACS800-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

Supply connection

Disconnecting device

Install a hand-operated input disconnecting device between the AC power source
and the drive. The disconnecting device must be of a type that can be locked to the
open position for installation and maintenance work.
EU
To meet the European Union Directives, according to standard EN/IEC 60204-1,
Safety of Machinery, the disconnecting device must be one of the following types:
Switch-disconnector of utilization category AC-23B (EN 60947-3)
Disconnector that has an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of the
disconnector (EN 60947-3)
Circuit breaker suitable for isolation in accordance with EN 60947-2
US
The disconnecting device must conform to the applicable safety regulations.

Fuses

Thermal overload and short-circuit protection
See

Main contactor

If used, dimension the contactor according to the nominal voltage and current of the
drive. The utilization category (IEC 947-4) is AC-1.
Planning the electrical installation 45
(page 46).