Other pump control algorithms

Set relays to Alternate Duty Backup

Parameter
2.8.1.4. Relay Function
2.8.1.4. Relay Function
2.8.1.4. Relay Function
Set the Relay ON Setpoints
Parameter
2.8.1.5. ON Setpoint
2.8.1.5. ON Setpoint
2.8.1.5. ON Setpoint
Set the Relay OFF Setpoints
Parameter
2.8.1.6. OFF Setpoint
2.8.1.6. OFF Setpoint
2.8.1.6. OFF Setpoint

Set relays to Fixed Duty Assist

Parameter
2.8.1.4. Relay Function
2.8.1.4. Relay Function
2.8.1.4. Relay Function
Set the Relay ON Setpoints
Parameter
2.8.1.5. ON Setpoint
2.8.1.5. ON Setpoint
2.8.1.5. ON Setpoint
Set the Relay OFF Setpoints
Parameter
2.8.1.6. OFF Setpoint
2.8.1.6. OFF Setpoint
2.8.1.6. OFF Setpoint
Page 86
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Index
Mode
1
Alternate Duty Backup Sets the pump relays
2
Alternate Duty Backup
3
Alternate Duty Backup
Index
Value Description
1
0.4 m Sets the three setpoints for the pump
relays. The first cycle will use these
2
0.3 m
setpoints. Subsequent cycles rotate
3
0.2 m
the setpoints among the pumps.
Index
Value Description
1
1.3 m
Sets the three setpoints for the pump
relays.
2
1.3 m
3
1.3 m
Index
Mode
1
Fixed Duty Assist Sets the pump relays (Relays
2
Fixed Duty Assist
3
Fixed Duty Assist
Index
Value Description
1
0.4 m Sets the three setpoints for the pump
relays. The setpoints remain attached
2
0.3 m
to the pump relays.
3
0.2 m
Index
Value Description
1
1.3 m
Sets the three setpoints for the pump
relays.
2
1.3 m
3
1.3 m
Description
(Relays 1, 2, and 3) to
Alternate Duty Backup.
Description
1, 2, and 3) to Fixed Duty
Assist. Multiple pumps can
run simultaneously.