Siemens HydroRanger 200 HMI Operating Instructions Manual page 138

Ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Alters
Altered by
Related
Enter a value reflecting maximum application range.
Always prevent the monitored surface from approaching within 0.3 m (1 ft) of
the transducer face as this is the minimum blanking for most Siemens
transducers (some require more blanking – see your transducer manual).
Many other parameters are set as a percentage of span (even if they are
entered in
span is altered after installation and the other parameters are measured using
a level determined upward from the Empty level toward the transducer face.
All volumes are based on span so it should be set for the maximum volume
point if volume calculations are needed.
2.2.3. Transducer Selector
Sets the transducer index for all parameters applicable to this sub-menu.
2.2.4. Empty
Enters distance, in 2.1.1. Units, from the face of the transducer to the process
empty point.
Index
Values
Alters
Altered by
Related
Setting this value also sets
value. For distance operation (
Empty.
Page 128
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
2. 1 3.4.5. Zero Head
2.8. 1 .5. ON Setpoint
2.8. 1 .6. OFF Setpoint
2. 1 . 1 . Units
2.2.4. Empty
2.7. Volume
2.2.6. Blanking
3.2.6.3. Level
3.2.6. 1 1. Space
3.2.6. 1 3. Head
2.1. 1 . Units
). The values of these other parameters may change if the
Transducer
Range: 0.000 to 99.000 m (or equivalent, depending on
Preset: 5.000 m (or equivalent, depending on
2.2.2. Span
2. 1 . 1 . Units
2.2.6. Blanking
3.2.6.3. Level
3.2.6.4. Distance (%)
2.2.2. Span
2.1.3. Sensor Mode
Empty
Span
2. 1 . 1 . Units
, unless Span was already set to another
= Distance), Span is preset to
100%
0%
2. 1 . 1 . Units
)
)
A5E36281317