Backup Level Override; Backup Level Override Parameters - Siemens HydroRanger 200 HMI Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Backup level override

Backup level override provides the option of overriding the ultrasonic input with another
contacting point level device (for example, the Pointek CLS200). The ultrasonic reading is
fixed at the programmed switch level until the discrete input is released; the override is
then removed, and the HydroRanger 200 HMI returns to normal measurement.

Backup level override parameters

2.9.1.2. Discrete Input Number
Sets the discrete input as the source of a level reading override.
2.9.1.3. Level Override Value
Substitutes value for current reading when
Value is added in current units and is valid only for the following:
Level
Space
Distance
Difference
Average modes of operation
Head level in OCM mode
Example:
A high level backup switch is connected to Digital Input 2 in the same application as
Transducer 1 at level value 4.3 m.
Settings
Parameter
2.9.1.2. Discrete Input Number
2.9.1.2. Discrete Input Number
2.9.1.3. Level Override Value
2.9.1.3. Level Override Value
When the level rises to 4.3 m and the switch is activated, the reading is forced to 4.3 m
where it stays until the switch is de-activated.
2.9.1.4. Override Time Delay
Sets the time (in seconds) used to calm the override condition input.
Page 72
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
2.9.1.2. Discrete Input Number
Index
Value
1
DI 2 Override Signal
2
*No Override
1
4.3
2
is activated.
A5E36281317