2.12.2. LCD Contrast
Adjusts the luminance of the bright and dark colors of the display.
Options
The factory setting is for optimum visibility at room temperature and in average
lighting conditions. Extremes of temperature will lessen the contrast. Adjust
the value to improve visibility in different temperatures and lighting conditions.
2.12.3. Level Selector
Sets the Level Point index for all parameters applicable to this sub-menu.
2.12.4. Decimal Position
Defines the maximum number of decimal places used on the LCD.
Index
Options
Alters
Altered by
Related
In RUN mode, the decimal position adjusts to prevent the number of digits from
exceeding the display capabilities. To keep the decimal place from shifting,
reduce the number of decimal places to that shown at 100%.
Example: If 100% is 15 m, use two decimal places for sample readings of 15.00
or 12.15.
2.12.5. Convert Reading
Multiplies the current value by the specified amount, to allow for scaling.
Index
Values
Related
Examples:
Page 178
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Range: 0 (Low contrast) to 20 (High contrast)
Preset: 10
Level
No digits
1 digit
*2 digits
3 digits
2. 1 3.4.6. Flowrate Decimal
2.7.3. Maximum Volume
3.2.6.2. Reading
Level
Range: -999 to 9999
Preset: 1.000
3.2.6.2. Reading
If the measured value is in feet, enter 0.3333 to display the number of
yards.
For simple linear volume conversions, set
then enter the volume measurement per unit to get the correct
2.1.1. Units
to 1 (meter) and
A5E36281317