Volume
Volume is used in two situations:
1.
Calculate and display Volume instead of Level.
2.
Calculate pumped volume to accomplish the following:
•
Totalize the volume of material that is pumped out of the wet well.
•
Set an alarm on pump efficiency.
Readings
When using volume, volume values are presented in the same units specified in
Maximum Volume
The default is 100, which gives a reading in percent of total. Use whatever unit is
applicable. If the value is too large for the six-digit LCD, use a larger unit.
Vessel shape and dimensions
The HydroRanger can be configured to suit many common vessel or tank shapes. (See
2.7.2. Vessel Shape
selections.) Each shape uses the Empty distance (
volume.
Some tank shapes also require extra dimensions to calculate the volumes. Do not
estimate these values as they must be exact to ensure the accuracy of your volume
calculations.
A
Parameter
2.7.2. Vessel Shape
2.7.3. Maximum
Volume
2.7.4. Dimension A
Notes:
•
The default reading changes to a range from 0 to 100 (the value in
Maximum Volume
2.2.4. Empty
•
Empty (
Page 76
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
.
on page 134. Whenever possible, use one of those pre-defined
To configure volume for a tank with a half-sphere bottom, set the
following:
Index
Mode/Value
1
Half Sphere
1
1
).
) is still measured to the bottom of the tank, not the top of A.
2.2.4. Empty
) in its calculations of
Description
Selects the correct tank shape
Bottom
100
Sets maximum volume at 100
(percent).
1.3
Sets A to 1.3 m
2.7.3.
2.7.3.
A5E36281317