Siemens HydroRanger 200 HMI Operating Instructions Manual page 273

Ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is
shown in the register as 5402.
Pumped volume (R41,440 – R41,443)
The pumped volume registers hold the current total for all of the pumps associated
with a level point. These registers are available only if operation is set to pumped
2.1.3. Sensor Mode
volume (
These volumes can become very large. Therefore, two registers are used to hold the
Unsigned double precision integer (UINT32) on page 268
value. See
The value in the registers is given as an integer value but must be interpreted as having
the number of decimals set in
Ensure that your software accounts for these decimal places before you report the
pumped volume totals.
Pump hours (R41,450 – R41,461)
The number of running hours for the referenced pump relay. The hours are given to three
decimal places, so the integer must be divided by 1000 to get the correct value. For
example 12,340 represents 12.34 hours.
This value comes from parameter
Pump starts (R41,470 – R41,475)
The number of pump starts for the referenced pump relay.
This value comes from parameter
Parameter access (R43,998 – R46,999)
Parameter values are given as integers in the range of registers from R44,000 to R44,999.
The last three numbers of the register correspond to the parameter number.
Parameter Register #
44,000
44,001
44,002
...
44,999
Usually, the parameters are all read / write.
Note:
• Parameters
3.2. 1 . Master Reset
• Parameter
Data types on page 268
• See
different parameters.
Each parameter register has a corresponding format register that holds the format
information required to interpret the value. See
page 266
.
A5E36281317
= Pump Totalizer).
2. 1 4.4. Totalizer Decimal Position
3.2.7.2. Pump Hours
3.2.7.4. Pump Starts
Format Register #
5.1. Write Protection
and
cannot be used via Modbus.
for a description of the types associated with
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
: this number can be 0 to 3.
. See page 190 for details.
. See page 190 for details.
46,000
46,001
46002
...
46,999
3.2. 1 . Master Reset
are Read only.
Format words (R46,000 to R46,999) on
for more information.
Parameter
5. 1 . Write Protection
2. 1 .3. Sensor Mode
2. 1 .6. Material
...
3.2. 1 . Master Reset
Page 263