Common problems chart

Symptom
Display blank, trans-
ducer not pulsing
Display blank, trans-
ducer is pulsing
Display active, trans-
ducer not pulsing
A5E36281317
Possible cause
No power, incorrect power
Loose or disconnected display
cable
Incorrect transducer connec-
tions or wiring;
Incorrect transducer selection
(or set to NO Transducer);
Transducer has been disabled
through the software
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Action
Check mains voltage at terminals.
Check fuse.
Check wiring connections.
Check wiring.
Reconnect display cable.
Verify terminal connections.
Check transducer field wiring.
Check any junction box connec-
tions.
Check that transducer is enabled
2.1.5. Transducer
(see
118).
on page