Other Pump Control algorithms
Set Relays to ALTERNATE DUTY BACKUP (ADB)
Parameter
2.7.1.4. Pump Control Mode
or
2.7.1.5. Pump Control Mode
Set the ON Setpoints
Parameter
2.7.1.6. ON Setpoint Pump 1
2.7.1.8. ON Setpoint Pump 2
Set the OFF Setpoints
Parameter
2.7.1.7. OFF Setpoint Pump 1
2.7.1.9. OFF Setpoint Pump 2
Set Relays to FIXED DUTY ASSIST (FDA)
Parameter
2.7.1.5. Pump Control Mode
Set the ON Setpoints
Parameter
2.7.1.6. ON Setpoint Pump 1
2.7.1.8. ON Setpoint Pump 2
Set the OFF Setpoints
Parameter
2.7.1.7. OFF Setpoint Pump 1
2.7.1.9. OFF Setpoint Pump 2
Page 82
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Value Description
ADB
Sets the control algorithm used to trip the pump
relay to ALTERNATE DUTY BACKUP . Only one
pump can run at a time.
Sample
Description
Value
1.3 m
Sets the level at which pump 1 turns on. The
first cycle will use this setpoint. Subsequent
cycles rotate the setpoint among the pumps.
1.2 m
Sets the level at which pump 2 turns on.
Sample
Description
Value
0.4 m
Sets the level at which pump 1 turns off. The
first cycle will use this setpoint. Subsequent
cycles rotate the setpoint among the pumps.
0.3 m
Sets the level at which pump 2 turns off.
Value Description
FDA
Sets the control algorithm used to trip the pump
relay to FIXED DUTY ASSIST. Multiple pumps
can run simultaneously.
Sample
Description
Value
1.3 m
Sets the level at which pump 1 turns on.
1.2 m
Sets the level at which pump 2 turns on.
Sample
Description
Value
0.4 m
Sets the level at which pump 1 turns off.
0.3 m
Sets the level at which pump 2 turns off.
A5E33329501