Discrete inputs can be used for the following:
Passing other information to a remote system through communications.
Backup level override.
Use the parameters listed above to have discrete inputs modify the unit's operation.
To configure the discrete input itself, use the following parameters:
2.9.1. Backup Level Override
Overrides the transducer reading by a discrete input, such as a contacting
point device. The transducer reading will be fixed at the programmed override
value until the discrete input is released.
The device makes decisions based on the override values.
2.9.1.1. Transducer Selector
A5E36281317
Delay Between Starts
Sets the minimum delay (in seconds) between pump starts.
This delay determines when the next pump is permitted to
start.
Index
Values
Related
Power Resumption Delay
Sets the minimum delay before the first pump restarts after
power failure.
Index
Values
Related
This reduces power surge by not having the first pump start
immediately upon power resumption. When this delay expires,
other pumps will start as per
Sets the transducer index for all parameters applicable to this sub-
menu.
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Global
Range: 0.0 to 9999
Preset: 10 seconds
2.8.2.7. 1 . Run-ON Interval
2.8.2.8.2. Power Resumption Delay
2.8.2.6.2. Level Setpoint Variation
2.8. 1 .8. Pump by Rate
Global
Range: 0.000 to 9999
Preset: 10 seconds
2.8.2.7. 1 . Run-ON Interval
2.8.2.6.2. Level Setpoint Variation
2.8. 1 .8. Pump by Rate
2.8.2.8. 1 . Delay Between Starts
2.8.2.8.1. Delay Between Starts
.
Page 155