Communications installation

Wiring guidelines
The RJ-11 cable maximum length is 3 meters.
RS-485 maximum length is 1,200 meters (4,000 feet).
Use 24 AWG (minimum).
Use good quality communication grade (shielded twisted pairs) cable that is
recommended for RS-485 for port 2 (Belden 9842).
Run the communication cable separately from power and control cables (do not tie
wrap your RS-232 or RS-485 cable to the power cable or have them in the same
conduit).
Use shielded cable and connect to ground at one end only.
Follow proper grounding guidelines for all devices on the bus.
Improper wiring and incorrect choice of cables are two of the most common
Note:
causes of communication problems.
Ports 1 and 2
Port
Wall mount
RS-232 port (RJ-11 modular telephone jack) is generally used with a laptop com-
1
puter or modem.
2
Connections for the RS-485 port are on the terminal block.
Ports 1 and 2: RS-232 RJ-11 jack and RS-485 locations
The RJ-11 jack and the RS-485 port are inside the enclosure of the unit.
A5E36281317
RJ-11 jack
TRANSDUCER
1
WHT
2
2
BLK
3
WHT
1
4
BLK
5
SHLD
6
7
8
9
10
11
12
13
14
15
16
17
18
19
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
SERVICE
DISPLAY
12 - 30 V
BATTERY
INPUT POWER
OPTIONAL CARD
SYNC
20
21
22
SHLD
23
24
1
25
26
2
27
28
29
SHLD
30
1
31
2
32
DC
33
COM
34
A
35
B
36
RS-485 port
Page 255

Advertisement

Table of Contents
loading

Table of Contents