Communications installation
Wiring guidelines
•
The RJ-11 cable maximum length is 3 meters.
•
RS-485 maximum length is 1,200 meters (4,000 feet).
•
Use 24 AWG (minimum).
•
Use good quality communication grade (shielded twisted pairs) cable that is
recommended for RS-485 for port 2 (Belden 9842).
•
Run the communication cable separately from power and control cables (do not tie
wrap your RS-232 or RS-485 cable to the power cable or have them in the same
conduit).
•
Use shielded cable and connect to ground at one end only.
•
Follow proper grounding guidelines for all devices on the bus.
Improper wiring and incorrect choice of cables are two of the most common
Note:
causes of communication problems.
Ports 1 and 2
Port
Wall mount
RS-232 port (RJ-11 modular telephone jack) is generally used with a laptop com-
1
puter or modem.
2
Connections for the RS-485 port are on the terminal block.
Ports 1 and 2: RS-232 RJ-11 jack and RS-485 locations
The RJ-11 jack and the RS-485 port are inside the enclosure of the unit.