Siemens HydroRanger 200 HMI Operating Instructions Manual page 62

Ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Zero Head
The distance above 2.2.4. Empty, in 2.1.1. Units representing zero head (and zero
flow).
Index
Values
This feature can be used for most weirs and some flumes (e.g. Palmer-Bowlus)
where the zero reference is at a higher elevation than the channel bottom
Maximum Flow
The maximum flowrate associated with 2.13.4.2. Maximum Head.
Index
Values
This represents the flow at the highest head level supported by the PMD and works
in conjunction with
exponential curve. Use it when the PMD requires a maximum head and flow
reference point. This would include Exponential, Palmer-Bowlus Flume, H-Flume,
and Universal breakpoints.
Also, use this parameter with
The limitation of four digits is for the LCD only, and the flowrate value is available
with greater precision through communications.
Notes:
• The display of the measured value is limited to six digits. A Maximum Flow
value larger than seven characters will not display correctly.
• If measured value is larger than seven characters, the screen displays ####. A
larger unit (
points (
Flowrate Decimal
The maximum number of decimal places to be displayed.
Index
Options
Page 52
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Single-point model
Global
Range: -999 to 9999
Preset: 0.000
Single-point model
Global
Range: -999 to 9999
Preset: 1000
2.13.4.2. Maximum Head
2.13.4.4. Flow Time Units
2. 1 3.4.4. Flow Time Units
2.13.4.6. Flowrate Decimal
Single-point model
Global
No digits
1 digit
*2 digits
3 digits
Dual-point model
Transducer
Dual-point model
Transducer
to define the highest point in the
to define the flowrate units.
) should be used, or number of decimal
) should be reduced.
Dual-point model
Transducer