Siemens HydroRanger 200 HMI Operating Instructions Manual page 207

Ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

3.2.7.5. Pump Run-ONs
3.2.8. Temperature Peak Values
The following features display the high and/or low temperatures in °C.
If the unit is powered up without a temperature sensor connected, the value –
50°C is displayed. This information can help trace problems with both built-in
and external temperature sensors.
3.2.8.1. Transducer Selector
3.2.8.2. Transducer Temperature Maximum
3.2.8.3. Transducer Temperature Minimum
3.2.8.4. TS-3 Temperature Maximum
A5E36281317
Shows or resets the accumulated number of times the selected relay
has been held ON via 2.8.2.7. 1 . Run-ON Interval.
Relay
Index
Range: 0 to 9999
Values
2.8. 1 .4. Relay Function
Related
To change the relay assignment, see
Sets the transducer index for all parameters applicable to this sub-
menu.
Shows the highest temperature encountered, as measured by the
temperature sensor in the transducer (if applicable).
Transducer
Index
Range: - 50 to 150°C (Read only)
Values
Preset: - 50°C
3.2.8.3. Transducer Temperature Minimum
Related
To reset the log after a short circuit on the transducer wiring, enter
the value -50.
Shows the lowest temperature encountered, as measured by the
temperature sensor in the transducer (if applicable).
Transducer
Index
Range: - 50 to 150°C (Read only)
Values
Preset: 150°C
3.2.8.2. Transducer Temperature Maximum
Related
To reset the log after an open circuit on the transducer wiring, enter
the value 150.
Shows the highest temperature encountered, as measured by the TS-
3 temperature sensor (if applicable).
Global
Index
Range: - 50 to 150°C (Read only)
Values
Preset: - 50°C
3.2.8.5. TS-3 Temperature Minimum
Related
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
3.2.7.1. Relay Selector
.
Page 197