Product ID (R40,064)
This value identifies the Siemens device type:
Device Type
HydroRanger 200
HMI
Point data (R41,010 – R41,031)
Level Point data contain the current instrument readings. These are the values shown for
the reading measurement for each Level Point. The reading is based on the setting for
2. 1 .3. Sensor Mode
117 for details.
The measurement registers are 41,010 to 41,012. The HydroRanger 200 HMI uses 41,010
when configured with a single transducer and 41,010 to 41,012 when configured with two
2.8. 1 .4. Relay Function
transducers (
transducers can create three readings because they can generate an average or
differential reading (R41,012) as well as the two level readings (R41,010 and R41,011).
Available registers:
Data
Reading
Volume
Temperature
The reading is expressed as a percentage of full scale, multiplied by 100:
Reading
0
5000
7564
20,000
Totalizer (R41,040 – R41,043)
The totalizers are stored as 32-bit integers using two registers. The totalizers can be read
with R41,040 and R41,041 as totalizer for Point 1, and R41,042 and R41,043 as totalizer for
Point 2. The totalizer values can be reset to any value by writing that value to the
registers. The values can be cleared by writing zero (0) to the registers.
Input/Output (R41,070 – R41,143)
The HydroRanger 200 HMI has discrete inputs, mA inputs, mA outputs and relay outputs.
See below for details for each I/O type.
A5E36281317
Value
32
, which can be set to Level, Distance, OCM Flow, or Volume. See page
= Rate of Change or Temperature only). Two
Registers
41,010 to 41,012
41,020, 41,021
41,030 and 41,031
Value
0.00%
50.00%
75.64%
200.00%
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Parameter
3.2.6.2. Reading
3.2.6. 1 3. Head
)
3.2.6. 1 7. Transducer Temperature
Page 261