General fault codes

If two faults are present at the same time, the device status indicator and text for the
Note:
fault with the higher priority will display.
HMI
Priority
icon
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Page 218
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Fault #
Fault text
14
Trans. 1 Loss of Echo
15
Trans. 2 Loss of Echo
1
TS-3 short (TB:28/29)
2
Trans. 1 open (TB:1/2)
3
Trans. 2 open (TB:3/4)
4
Trans. 1 short (TB:1/2)
5
Trans. 2 short (TB:3/4)
6
Trans. 1 short (TB:1/2)
7
Trans. 2 short (TB:3/4)
Trans. 1 error (TB:1/2)
8
Trans. 2 error (TB:3/4)
9
Point 1 Temp. open
10
Point 2 Temp. open
11
Point 1 Temp. Error
12
Point 2 Temp. Error
13
Cause
Point 1 fail-safe.
Point 2 fail-safe.
TS-3 terminals shorted.
Transducer 1 open.
Transducer 2 open.
Transducer 1 short.
Transducer 2 short.
Transducer 1 short.
Transducer 2 short.
Transducer 1 specified
incorrectly, connections
reversed, faulty internal
temp sensor.
Transducer 2 specified
incorrectly, connections
reversed, faulty internal
temp sensor.
Temp sensor assigned to
Point 1 open.
Temp sensor assigned to
Point 2 open.
Temp sensor assigned to
Point 1 reversed, shorted
cable, temp sensor failed.
Temp sensor assigned to
Point 2 reversed, shorted
cable, temp sensor failed.