Pump control

Setting a Pump Down Group

Example: Sewage wet well
Set a group of three pumps to pump down a wet well.
Inflow
Set the common parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Parameter
2. 1 .3. Sensor Mode
2. 1 .6. Material
2.3.4. Response Rate
2. 1 .5. Transducer
2. 1 . 1 . Units
2.2.4. Empty
2.2.2. Span
1.
Example assumes a single measurement unit. If your HydroRanger 200
HMI has dual-point software installed, then some parameters are indexed
by two level points.
A5E36281317
2.2.4. Empty
2.2.2. Span
Value/
1
Index
Mode
Global
*Level
Global
Liquid
Global
Medium Maximum Process Speed = *Medium (1.0
Global
XPS-10
Global
Meters
Global
1.8
Global
1.4
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
HydroRanger
200 HMI
Outflow
Description
Operation = *Level
Material = *Liquid
m/min)
Transducer = XPS-10 (single-point preset)
Units = Meters
Empty = 1.8 m
Span = 1.4 m
Page 83