General Operation
7.7 Pump Control
7.7.2.4

Set the OFF Setpoints

Parameter
OFF Setpoint Pump 1
(2.7.1.7.) (Page 190)
OFF Setpoint Pump 2
(2.7.1.9.) (Page 191)
Sample values denoted by asterisks in illustration on Setting a pump down (wet well) group
1)
(Page 104).
7.7.3

Other Pump Control algorithms

7.7.3.1

Set Relays to ALTERNATE DUTY BACKUP (ADB)

Parameter
Pump Control Mode
(2.7.1.4.) (Page 189) or
Pump Control Mode
(2.7.1.5.) (Page 189)
Set the ON Setpoints
Parameter
ON Setpoint Pump 1
(2.7.1.6.) (Page 190)
ON Setpoint Pump 2
(2.7.1.8.) (Page 190)
106
Sample Value
Description
1
0.5 m**
Sets the level at which pump 1 turns off. The first
cycle will use this setpoint. Subsequent cycles
rotate the setpoint among the pumps. For exam-
ple: In cycle 1, pump 1 turns off at 0.5 m. In the
next cycle, pump 2 will turn off at 0.5 m.
0.6 m**
Sets the level at which pump 2 turns off.
Value
ADB
Sample
Description
Value
1.3 m*
Sets the level at which pump 1 turns on. The first cycle will use
this setpoint. Subsequent cycles rotate the setpoint among the
pumps.
1.2 m*
Sets the level at which pump 2 turns on.
Description
Sets the control algorithm used to trip the
pump relay to ALTERNATE DUTY BACKUP.
Only one pump can run at a time.
Operating Instructions, 04/2021, A5E33329501-AG