Alternate Duty Assist - Siemens HydroRanger 200 HMI Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Alternate Duty Assist

2.8.1.4. Relay Function = Alternate Duty Assist alternates the lead pump each time the
material level cycles and runs all pumps together.
Relay operation
2.8. 1 .11. Relay Logic
(for
The setpoints associated with the relays are grouped so that they can be rotated.
Setpoint 1 does not relate directly to Relay 1. The pumping algorithm manages the
mapping of setpoints to relays.
When pumps are run, they RUN in parallel.
Relay table
Cycle 1
Relays
ON 3
ON 2
ON 1
OFF
Cycle 2
Relays
ON 3
ON 2
ON 1
OFF
Cycle 3
Relays
ON 3
ON 2
ON 1
OFF
Alternate Duty Backup
2.8.1.4. Relay Function = Alternate Duty Backup alternates the lead pump each time the
material level cycles.
Relay operation
2.8. 1 .11. Relay Logic
(for
The setpoints associated with the relays are grouped so that they can be rotated.
Setpoint 1 does not relate directly to Relay 1. The pumping algorithm manages the
mapping of setpoints to relays. When pumps are run, they can RUN only one at a time.
Page 250
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
= Positive)
1
2
ON
ON
ON
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
1
2
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
1
2
ON
ON
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
= Positive)
3
3
3
A5E36281317