Troubleshooting
Notes:
• Many of the parameters referenced and techniques described here require a good
understanding of ultrasonic technologies and Siemens echo processing software. Use
this information with caution.
• If the setup becomes too confusing, do a
Communication troubleshooting
General
1.
Check the following:
•
There is power at the device.
•
The HMI is showing the relevant data.
•
The device can be programmed using the local push buttons.
•
If any fault codes are being displayed, see page 218 for a detailed list.
2.
Verify that the wiring connections are correct.
3.
A HydroRanger 200 HMI parameter is set via remote communications, but the
parameter remains unchanged.
•
Try setting the parameter from the local push buttons. If it cannot be set using
the buttons, ensure
If you continue to experience problems, check the FAQ on our website:
www.siemens.com/HydroRanger, or contact your Siemens representative.
A5E36281317
5. 1 . Write Protection
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
3.2.1. Master Reset
and start again.
is set to the unlock value (1954).
Page 217