Siemens HydroRanger 200 HMI Operating Instructions Manual page 148

Ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

2.5.9. Milliamp Output
Displays the current mA output value.
Values
2.5.10. Fail-safe Mode
Use for fail-safe operation, independent of the 2.4.5. Material Level.
Index
Options
Related
2.5.11. 4 mA Output Trim
Calibrates the 4 mA output.
Index
Values
Related
Adjust this value so the device indicates 4.00 mA when
is accessed.
Trimming the 4 mA value:
1. Go to
2. Read the value indicated on the current meter or other connected
device, and enter it in
The new trimmed value will be shown in the current meter or other
connected device.
2.5.12. 20 mA Output Trim
Calibrates the 20 mA output.
Index
Values
Related
Adjust this value so the device indicates 20.00 mA when
Trim
is accessed.
Trimming the 20 mA value:
1. Go to
2. Read the value indicated on the current meter or other connected
device, and enter it in
The new trimmed value will be shown in the current meter or other
connected device.
Page 138
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Range: 3.500 to 22.2 mA
mA Output
*OFF
mA output responds to
HI
Produce the Span mA output immediately.
LO
Produce the Empty mA output immediately.
Hold
Last known value is held until normal operation resumes.
mA output goes to user-selected value defined in
Value
mA Fail-safe Value
2.5.3. Current Output Function
mA Output
Preset: 4.00
2.5. 1 2. 20 mA Output Trim
2.5.9. Milliamp Output
2.5. 1 1. 4 mA Output Trim
mA Output
Preset: 20.00
2.5. 1 1. 4 mA Output Trim
2.5.9. Milliamp Output
2.5. 1 2. 20 mA Output Trim
2.4.5. Material Level
.
2.5. 1 1. 4 mA Output Trim
and enter 4.00 mA
.
.
2.5. 1 2. 20 mA Output
and enter 20.00 mA
.
.
.
2.4.9.
A5E36281317