Discrete inputs (R41,070)
This table shows the current status of the discrete inputs. Only register 41,070 is used.
Discrete Input
1
2
Relay outputs (R41,080)
This table shows the current status of the relays. A reading of 0 means that the relay
function is not asserted and a 1 means that it is asserted. For example, a 1 for a pump
relay means that the pump is running.
Relay
1
2
3
4
5
6
Values are written to control a relay only if the Relay Control Function (
Function
) is set to Communication. See
on page 271
.
mA Input (R41,090)
The mA input is scaled from 0 to 2,000 (0 to 20 mA multiplied by 100). Parameter
Scaled mA Input Value
mA Output (R41,110-41,111)
The mA output is scaled from 0 to 2,000 (0 to 20 mA multiplied by 100). This is displayed in
2.5.9. Milliamp Output
Pump control (R41,400 – R41,474)
Only relays set for pump control (
Backup, or Alternate Duty Assist) are available. These registers have no effect on relays
programmed for other uses.
Pump ON setpoint (R41,420 – R41,425)
The ON setpoint level (
The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is
shown in the register as 5402.
Pump OFF setpoint (R41,430 – R41,435)
The OFF setpoint level (
Page 262
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Data Address
41,070, bit 1
41,070, bit 2
Data Address
41,080, bit 1
41,080, bit 2
41,080, bit 3
41,080, bit 4
41,080, bit 5
41,080, bit 6
Relay function codes (2.8.1.4. Relay Function Only)
displays the value of the input. It is indexed by the input number.
.
2.8.1.4. Relay Function
2.8. 1 .5. ON Setpoint
) for the referenced pump relay.
2.8. 1 .6. OFF Setpoint
) for the referenced pump relay.
2.8. 1 .4. Relay
= Fixed Duty Assist, Fixed Duty
A5E36281317
2.6.5.