Set the common parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Parameter
2. 1 .3. Sensor Mode
2. 1 .6. Material
2.3.4. Response Rate
2. 1 .5. Transducer
2. 1 . 1 . Units
2.2.4. Empty
2.2.2. Span
1.
Example assumes a single measurement unit. If your HydroRanger 200
HMI has dual-point software installed, then some parameters are indexed
by two level points.
Set relays to Alternate Duty Assist
Parameter
2.8.1.4. Relay Function
2.8.1.4. Relay Function
2.8.1.4. Relay Function
Set the Relay ON Setpoints
Parameter
2.8.1.5. ON Setpoint
2.8.1.5. ON Setpoint
2.8.1.5. ON Setpoint
Set the Relay OFF Setpoints
Parameter
2.8.1.6. OFF Setpoint
2.8.1.6. OFF Setpoint
2.8.1.6. OFF Setpoint
For more information, see
A5E36281317
Index
Global
Global
Global
Global
Global
Global
Global
Index
1
Alternate Duty Assist
2
Alternate Duty Assist
3
Alternate Duty Assist
Index
1
2
3
Index
1
2
3
Appendix B: Pump control reference
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Mode/
1
Description
Value
*Level
Operation = *Level
Liquid
Material = Liquid
Medium Maximum Process Speed =
*Medium (1.0 m/min)
XPS-10
Transducer = XPS-10 (single-
point preset)
-
Units = Meters
1.8
Empty = 1.8 m
1.4
Span = 1.4 m
Mode
Value Description
0.4 m Sets the three setpoints for the pump
relays. The first cycle will use these
0.3 m
setpoints. Subsequent cycles rotate
0.2 m
the setpoints among the pumps.
Value Description
1.3 m
Sets the three setpoints for the pump
relays.
1.3 m
1.3 m
Description
Sets the pump relays
(Relays 1, 2, and 3) to
Alternate Duty Assist.
on page 241.
Page 85