2.9.1.2. Discrete Input Number
2.9.1.3. Level Override Value
2.9.1.4. Override Time Delay
Page 156
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Sets the discrete input to act as the source for a Level reading
override.
Transducer
Index
*No Override
DI 1 Override Signal
Options
DI 2 Override Signal
2.9. 1 .3. Level Override Value
Related
This value is substituted for the current reading when the selected
discrete input is enabled and activated.
Transducer
Index
Range: 0.0 to 99.00 m or equivalent, depending on
Units
Values
Preset: 0.00
Current reading
Alters
2. 1 .3. Sensor Mode
2. 1 . 1 . Units
2.2.4. Empty
Related
2.2.2. Span
2.9. 1 .2. Discrete Input Number
Notes:
• Enter value in current
• Valid for Level, Space, and Distance.
• Volume is calculated based on the Backup Level.
Example
Transducer 1 is configured for a Level measurement. Digital Input 2 is
connected to a Hi Level Backup switch located a level of 4.3 m.
Parameter
2.9. 1 .2. Discrete Input Number
2.9. 1 .3. Level Override Value
When the level rises to 4.3 m, and the switch is activated, the reading
is forced to 4.3 m. The reading stays at 4.3 m until the switch is de-
activated.
Defines the time used to calm (debounce) the override condition
input.
Transducer
Index
2. 1 .1. Units
.
Index
1
1
2. 1 . 1 .
Value
2
4.3
A5E36281317