Synchronizing with another HydroRanger 200 HMI, or other Siemens instru-
ments (DPL+, SPL, XPL+, LU01, LU02, LU10, LUC500, Hydro+, EnviroRanger,
MiniRanger, SITRANS LUT400):
Mount the level monitors together in one cabinet.
Use a common power (mains) supply and ground (earth) for all units.
Interconnect the SYNC terminals of all level monitors
Set parameter Shot Synchro (2.1.13.) on page 120.
For assistance, contact your Siemens representative, or go to
www.siemens.com/processinstrumentation.

Power

Warning: Before applying power to the HydroRanger 200 HMI for the first time,
ensure any connected alarm/control equipment is disabled until satisfactory system
operation and performance is verified.
Notes for AC power connections:
• The equipment must be protected by a 15 A fuse or circuit breaker on all current-
carrying conductors in the building installation.
• A circuit breaker or switch in the building installation, marked as the disconnect
switch, must be in close proximity to the equipment and within easy reach of the
operator, and must disconnect all current-carrying conductors.
Note: Make sure that the
device is connected
to a reliable ground.

Digital communications

Wiring the HydroRanger 200 HMI for communications allows it to be integrated into a full
SCADA system or an industrial LAN.
The HydroRanger 200 HMI can also be directly connected to a computer running
SIMATIC PDM.
Page 24
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Other Siemens
transceiver
Ground
HydroRanger
MultiRanger
200 HMI
GND
L1
L2/N
A5E36281317