2.4.6. Fail-safe Advance
Sets the speed the HydroRanger advances to, and returns from, the Fail-safe
Material Level.
Index
Options
Related
2.4.7. mA Output Selector
Sets the mA Output index for all applicable parameters in this sub-menu
Options
2.4.8. mA Fail-safe Mode
Use for fail-safe operation, independent of the 2.4.5. Material Level.
Index
Options
Related
2.4.9. mA Fail-safe Value
Sets the mA value to be reported when the fail-safe timer expires.
Note:
value to be reported.
Index
Values
2.5. Current Output
Sets the parameters applicable to the current value of the mA output.
A5E36281317
Level
*Restricted
Immediate
Fast Back
2.3.4. Response Rate
2.4.2. LOE Timer
2.4.5. Material Level
2.3.2. Fill Rate/minute
2.3.3. Empty Rate/minute
*mA Output 1
mA Output 2
mA Output
*OFF
mA output responds to
HI
Produce the Span mA output immediately.
LO
Produce the Empty mA output immediately.
Hold
Last known value is held until normal operation resumes.
mA output goes to user-selected value defined in
Value
mA Fail-safe Value
2.5.3. Current Output Function
2.4.4. Fail-safe Mode
must be set to Value in order for the Material Level
mA Output
Range: 0 to 22 mA
Preset: 3.58 mA
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
Advances to/from Fail-safe Material Level as
2.3.4. Response Rate
set by
minute
2.3.3. Empty Rate/minute
, and
Fail-safe Material Level assumed right away.
Fail-safe Level Advance is restricted, return is
immediate.
2.4.5. Material Level
.
2.3.2. Fill Rate/
,
.
.
.
2.4.9.
Page 135