2.9.2. Discrete Input Logic
2.9.2.1. Discrete Input 1
2.9.2.2. Discrete Input 2
2.9.2.3. Discrete Input 1 Scaled State
2.9.2.4. Discrete Input 2 Scaled State
A5E36281317
Range: 0.0 to 9999
Values
Preset: 5 seconds
Related
Note: Activation of the Level Override is subject to the
measurement cycle. This can add up to four seconds to the overall
response time depending on operating conditions and
programming.
Changes the behavior of Discrete Input 1.
Forced OFF
Forced ON
Options
*
Normally Open
Normally Closed
Changes the behavior of the Discrete Input 2.
Forced OFF
Forced ON
Options
*
Normally Open
Normally Closed
Shows the current value of the discrete input after any scaling is
applied. Read only.
Discrete input
Index
Active
Modes
Inactive
Readings are updated continuously even in PROGRAM mode. The
value signals a level override event.
Shows the current value of the discrete input after any scaling is
applied. Read only.
Discrete input
Index
Active
Modes
Inactive
Readings are updated continuously even in PROGRAM mode. The
value signals a level override event.
HydroRanger 200 HMI – OPERATING INSTRUCTIONS
2.9. 1 .2. Discrete Input Number
2.9. 1 .3. Level Override Value
2.9.2. 1 . Discrete Input 1
Page 157