Replace the Motherboard (FRU)
34.
Reinstall the air divider.
The divider is mounted to the power supply side wall using two tabs that are inserted into slots
in the side wall.
a.
Position the air divider so that its two tabs align with the two slots in the
power supply side wall.
b.
Slide the air divider downwards so its tabs fully engage with the slots in the
power supply side wall.
Ensure that the flanges on the divider enter their respective slots on the side wall and that
the Fault Remind button extender is aligned with the button on the motherboard.
Insert cables (SAS, NVMe, ESM) into the air divider cable shield by gently
c.
prying the shield [A in the illustration below] away from the power supply
side wall enough to slide the cables inside one at a time; starting with SAS,
then NVMe (if present), then ESM.