9.2.4.4.1

Installing Batteries

Danger
7
Only V39113-W5123-E891 (12 V/7 Ah) batteries are released for connection to the
UPSC-DR/UPSM and installation in the ECR.
The use of other battery types is prohibited.
ECR is supplied with four batteries in a separate package. Proceed as follows to install the bat-
teries in the ECR:
Step
1.
Set the switches for battery voltage and line voltage on the ECR's front panel to
"Off" (see Section 9.2.4.1).
2.
Remove the battery fuse (ECR front panel) (see Section 9.2.4.1).
3.
Unplug all of the ECR's power and connection cables.
4.
Remove the ECR housing cover: To do this, remove the three screws at the rear
and slide the housing cover back.
5.
Remove the mounting screw [A] on the battery retainer [B].
6.
Remove the battery retainer and set aside.
P31003-H3550-S403-4-7620, 02/05
HiPath 3000 V5.0, HiPath 5000 V5.0, Service Manual
Expanding and Upgrading HiPath 3000
Activity
[B]
[A]
exup.fm
Expanding HiPath 3000
9-15